Select Page

MPOD Mix Crate

Mpod with integrated bus

Mpod EC and LX models can be customized to integrate a Wiener or a custom 3U to 6U bus backplane (VME, VME64x, cPCI, …). All voltages required from the backplane specifications are provided. When no rear transition modules are needed, these compact solutions allow saving money and space by reducing the number of needed crates, i.e. combining power supply with DAQ.

Further the MPOD mainframe is configurable to have all LV / HV connectors either on the front or rear side. Different control and monitoring options are offered. A combo interface with 10/100 Ethernet, CAN bus and USB-2 provides a variety of network capabilities. Local control is available by using the LCD display.

Features

  • 19″ rack mountable bin with module cage for 10 LV or HV modules, Ruggedized mechanics
  • Two mounting modes:  outputs at front- or at rear side
  • 8U bin for bottom cooling air intake, 9U high for front air intake, optional with dust filter
  • Modular design: fan tray and primary power supply easily removed
  • Module size 6U x 8PU, 220mm deep
  • LV and HV modules freely pluggable
  • High Voltage modules with 8, 16 or 32 channels of 0,5kV … 6kV, floating or common ground, up to 480 HV channels  per Mpod- mainframe possible
  • High precision modules
  • Resolution 12 bit (LV), 16/20 bit (HV)
  • LV/HV Controller with Ethernet, CANbus, USB interface, and interlock input
  • OPC server for TCP/IP
  • 94V – 265VAC world-wide auto-range AC input, with power factor correction, CE
  • Graphic display for monitoring and programming, single rotary/push- button operated (optional)
  • Dimensions: 19” x 460mm (depth) x 8U (bottom air intake) or 9U (front air intake)
  • Weight: ca. 20 Kg, depending on options

Ordering Information

Standard configurations (others possible by request).

TypeBus SlotsMpod SlotsAir Baffle or Special Slots
Mpod EC - VME64-mix8 + bus controller5 + Mpod controller1
Mpod LX - VME64x-mix8 + bus controller5 + Mpod controller1
Mpod EC - CPCI (3U)-mix85 + Mpod controller2

Technical Information

Specs:
Rated mains input range106- 230VAC ± 15% (90...265VAC)
Rated input currentSinusoidal 16A for suffix H input, 32A for suffix K input
Inrush current:limited to rated input current (cold unit)
Input fuse:external, internal on request
Isolation (Inp.- outp.)CE EN 60950, ISO 380, VDE 0805, UL 1950, C22.2.950
DC output power: 600 ... <3000W (92 …265VAC)  / 300W for MPOD micro
 
EMC Compatibility
EMA.EN 61 000-6-3:2001[RF emission]
EN 55 022:1998 + Corr:2001 + A1:2000  Class Bconducted noise
EN 55 022:1998+ Corr:2001 + A1:2000  Class Bradiated noise
EN 61 000-3-2:2001harmonics
EN 61 000-3-3:1995 +Corr:1997 +A1:2001flicker
EMBEN 61 000-6-2:2001 [immunity]
EN 61 000-4-6:1996 + A1:2001injected HF currents
EN 61 000-4-3:1996 + A1:1998 + A2:2001radiated HF fields  incl. ”900MHz”
EN 61 000-4-4:1995 + A1:2001Burst
EN 61 000-4-5:1995 + A1:2001Surge
EN 61 000-4-11:1994 + A1:2000voltage variations
EN 61 000-4-2:1995 + A1:1998 + A2:2001ESD
 
Operation temperature: 0… 50°C  ambient without derating,  Storage:-30°C ... +85°C
Temperature coefficient:< 0,2% / 10K
Stability: 10mV or 0,1%  /  24 hours, 25mV or 0,3%  /   6 month
(under constant conditions)
Current limits:adjustable to any lower level
Voltage rise characteristics: monotonic 50ms, processor controlled.
Overvoltage protection:crow bar protection trip off adjusted to 125% of nominal voltage  each output
DC Off (trip off):  within 5ms if >5% deviation from adjusted nominal values, after overload, overheat, overvoltage, undervoltage (bad status), and fan fail, if temperatures exceed 125°C at heat sinks Limits programmable. Outputs discharged by crow bars, when power supply tripped- or switched Off.
Efficiency:75% ... 85%, depends on used modules
M F O T (Maintenance Free Operation Time):
internal blowers:40°C ambient>65 000 h
25°C ambient100 000 h
electronics:40°C ambient>100 000 h
 