MPOD Mini Crate
The Mpod mini crate is the small and low cost option for the WIENER multi-channel high and low voltage power supply system. The Mpod mini mainframe can house up to 4 plug-in low or high voltage modules. The integrated Mpod controller card provides10/100 Ethernet, CAN bus and USB-2 interfaces.
High voltage modules are available with 8 up to 48 channels in the voltage range of 500V … 20kV. All low voltage modules have 8 channels with a maximum of 50W / channel in different voltage ranges. All HV and LV channels are individually controlled and monitored.
In order to tailor the system to the individual hardware needs Mpod mini can be configured as “low-voltage only”, “high voltage only” or “mixed configuration”. Local control is available by using the optional LCD display.
Features
- 19″ x 5U mini bin with module cage for 4 LV or HV modules, can be used as desktop, mini tower or rack mountable
- Versions available for HV only, LV only or mixed LV/HV
- 4 slots for modules, LV and HV modules freely combinable
- Up to 192 channels high voltage possible, ISEG EHS/EDS/EBS modules with 8 … 48 channels in a range of 100V up to 20kV, floating or common ground
- Up to 32 channels low voltage per chassis, WIENER MPV 8xxx series 8-channel low voltage modules in 0…8V up to 0….120V ranges
- built in primary power supply (600W), low noise and ripple
- integrated cooling fan
- Mpod controller card with Ethernet 10/100, CAN-bus and USB-2 interfaces, Interlock connector, optional with ISEG CC24 controller (linux OS with iCS web service, EPIC’s IOC, OPC and SNMP)
- Integrated web-server and TCP/IP communication via SNMP, OPC server, DHCP capable
- 94V – 265V world-wide auto-range AC input, with power factor correction, CE-conformity
- Dimensions: 19” (482mm) x 4U (178mm) x 480mm [whd], weight: ca. 25 kg
Ordering Information
Standard configurations (others possible by request).
Type | Graphic display | Slots | Primary HV-power | Output | Backplane |
---|---|---|---|---|---|
Mpod MINI | No | 4 | 600W | Front | HV/LV |
Mpod MINI - LX | Yes | 4 | 600W | Front | HV/LV |
Mpod MINI-HV | No | 4 | 600W | Front | HV |
Mpod MINI-HV-LX | Yes | 4 | 600W | Front | HV |
Mpod MINI-LV | No | 4 | - | Front | LV |
Mpod MINI-LV-LX | Yes | 4 | - | Front | LV |
Technical Information
Specs: | |
---|---|
Rated mains input range | 106- 230VAC ± 15% (90...265VAC) |
Rated input current | Sinusoidal 16A for suffix H input, 32A for suffix K input |
Inrush current: | limited to rated input current (cold unit) |
Input fuse: | external, internal on request |
Isolation (Inp.- outp.) | CE EN 60950, ISO 380, VDE 0805, UL 1950, C22.2.950 |
DC output power: | 600 ... <3000W (92 …265VAC) / 300W for MPOD micro |
EMC Compatibility | ||
---|---|---|
EMA. | EN 61 000-6-3:2001 | [RF emission] |
EN 55 022:1998 + Corr:2001 + A1:2000 Class B | conducted noise | |
EN 55 022:1998+ Corr:2001 + A1:2000 Class B | radiated noise | |
EN 61 000-3-2:2001 | harmonics | |
EN 61 000-3-3:1995 +Corr:1997 +A1:2001 | flicker | |
EMB | EN 61 000-6-2:2001 | [immunity] |
EN 61 000-4-6:1996 + A1:2001 | injected HF currents | |
EN 61 000-4-3:1996 + A1:1998 + A2:2001 | radiated HF fields incl. ”900MHz” | |
EN 61 000-4-4:1995 + A1:2001 | Burst | |
EN 61 000-4-5:1995 + A1:2001 | Surge | |
EN 61 000-4-11:1994 + A1:2000 | voltage variations | |
EN 61 000-4-2:1995 + A1:1998 + A2:2001 | ESD |
Operation temperature: | 0… 50°C ambient without derating, Storage:-30°C ... +85°C | |
Temperature coefficient: | < 0,2% / 10K | |
Stability: | 10mV or 0,1% / 24 hours, 25mV or 0,3% / 6 month | |
(under constant conditions) | ||
Current limits: | adjustable to any lower level | |
Voltage rise characteristics: | monotonic 50ms, processor controlled. | |
Overvoltage protection: | crow bar protection trip off adjusted to 125% of nominal voltage each output | |
DC Off (trip off): | within 5ms if >5% deviation from adjusted nominal values, after overload, overheat, overvoltage, undervoltage (bad status), and fan fail, if temperatures exceed 125°C at heat sinks Limits programmable. Outputs discharged by crow bars, when power supply tripped- or switched Off. | |
Efficiency: | 75% ... 85%, depends on used modules | |
M F O T (Maintenance Free Operation Time): | ||
internal blowers: | 40°C ambient | >65 000 h |
25°C ambient | 100 000 h | |
electronics: | 40°C ambient | >100 000 h |