MARATON low voltage power supply system for hazardous HE
The high density very powerful and compact low-voltage floating power supply system MARATON possesses in a 3U high box 12 independent channels of 300W each. In parallel operation the output power per channel can be boosted to 600W / 900W /1200W... with 6 / 4 / 3... channel utilization.
Dynamic behavior adjustable by internal jumper (long-short sensed distances to loads). .
- up to 12 independent, potential free outputs, total up to 3 kW DC output power (nom. 385VDC inp.), 3,6kW water cooled
- Fully controlled, adjustable trip levels
- Adjustable voltages, current limits and OVP-trip levels
- Extremely low noise and ripple
- CE conform EN 50 081/82 part 2 or 1, safety in accordance with EN 60 950
- 385V DC input for low cross section cabling
- VME compatible remote monitoring and control module for 12 channels with Ethernet (TCP/IP) interface (for Standard Environment)
- Water cooled (recommended) or by forced air
| Standard power modules (other possible on request) |
|
|
Type AL
for B-field up to <300G |
Optimal Voltage range |
Channels per module |
Peak output / Power
|
|
MDC |
|
2 |
2 x 55A or 1 x 110A / 330W (660W total) |
|
MDC |
|
2 |
2 x 22A or 1 x 44A / 330W (660W total) |
|
MDC |
7V ... 24V |
2 |
2 x 11,5A or 1 x 23A / 275W (550W total) |
|
MDC |
|
2 |
2 x 6,6A or 1 x 13,2A / 330W (660W total) |
|
|
|
|
|
Type FE
for B-fields up to <1200G |
Optimal Voltage range |
Channels per module |
Peak output / Power |
|
MDM |
2V ... 7V/8V |
2 |
2 x 55A or 1 x 110A / 330W (660W total) |
|
MDM |
5/7V ... 15/16V |
2 |
2 x 22A or 1 x 44A / 330W (660W total) |
|
MDM |
|
2 |
2 x 11,5A or 1 x 23A / 275W (550W total) |
|
MDM |
|
2 |
2 x 6,6A or 1 x 13,2A / 330W (660W total) |
|
Radiation tests
|
2000
2002
2002
2002/2004
2005 |
PSI
Louvain
Dijon, valuation test, fully equipped unit |
722Gy
417Gy
SEE, 14krad, p/ 60MeV
SEE |
7.99E+12 n/cm²
7.69E+12 n/cm²
1,00E+11 p/cm²
1,00E+11 p/cm² / 3,00E+11 p/cm²
5,60E+12 n/cm² |
|
3U box (max. 6 power modules) with 385VDC input +/-20V (plugged). With reduced output performance also connectable to 230VAC. Direct 3-phase AC input optionally. With direkt AC mains feeding power factor correction is not effected |
|
Regulation fast remote sense circuit (short sensed distance): |
|
static: |
|
MDC/M 2-8V |
<15mV |
(+/-100% load, +/- full mains range) |
|
MDC/M other voltages |
<0.05% |
(+/-100% load, +/- full mains range) | |
|
dynamic: (0.5m wire) |
|
MDC/M 2-8V |
<100mV |
(+/-25% load) |
|
Other |
<0.7% |
(+/-25% load) | |
|
Recovery time: (0.5m wire) |
|
+/-25% load |
within +-1% deviation |
within +-0.1% deviation |
|
MDC/M 2-8V |
0.2ms |
0.5ms |
|
MDC/M 30-60V |
0.5ms |
1.0ms |
|
MDC/M 5-16V / 7-24V |
0.0ms |
1.0ms | |
|
Conditions: |
Current slope <1000A/ms, 20mF per 100A parallel to load |
|
Regulation slow remote sense circuit (long sensed distance): |
|
static: |
|
MDC/M 2-8V / 30-60V |
<15mV |
(+/-100% load, +/- full mains range) |
|
Other |
<0.05% |
(+/-100% load, +/- full mains range) | |
|
dynamic: |
dynamic deviation depends on current slope resp. filter capacitors at load side only
30m cable to load, 0,3mF capacitance at load side, 1V drop at nominal load,
+/-80% load change with 3ms slope (50A output= 13,33A/ms) leads to less than 10% temporary output voltage deviation |
|
Recovery time: (40m wire, 5V at load side, Udrop <2V ) |
|
+/-25% load (<1000A/ms) |
within +/- 10% deviation |
within +/- 1% deviation |
|
MDC/M 30-60V / 7-24V |
<15ms |
<33ms |
|
Other |
<15ms |
<25ms |
Regulation timing adaptable to dynamic conditions (induced by cable length, voltage drops, sinker and filter capacities at load side) |
|
DC output characteristics: |
|
Sense compensation range: |
limited to < 10V or nom voltage (except special versions) |
|
Sense mode: |
closed loop and continuously controlling regulator to load |
|
Floating Range: |
>nominal output voltage for MEH, min. +/-10V for voltage ranges < 7V MEH and MDL |
|
Noise and ripple: |
|
0.5m wire: |
< 10mVpp (>7V: <15mVpp) |
(0-20MHz ) <2mVRMS(0-30MHz) |
|
10m wire: |
< 3mVpp <3mVRMS |
(0-300MHz) | |
|
Conditions, at load side: |
Parallel (X) 330µF and 1µF ceramic, 100nF HF- conducting to case (Y) each line |
|
Emission: |
CE EN 50081-1 (EN 55 022-B) |
|
Immunity: |
CE EN 50082-1 or 2 |
|
Operation temperature: |
0....50°C without derating, storage: -30°C till 85°C |
|
Temp.- Coefficient: |
< 0.2% / 10K |
|
Stability (Condition const.): |
<5mV or 0.1% within 24 h, <25mV or 0.3% within 6 months |
|
Current limiting: |
fast protection programmable to lower than peak values via trim-pots (constant current mode) via Remote Controller channel wise Imax trip off set point programmable independently |
|
Status control / DC Off (trip off): |
processed in external Remote Controller. Tripping global, group- or channel wise programmable (after overload, overheat , overvoltage, undervoltage) |
|
DC On / Off |
via Remote Controller |
|
Interlock input: |
optional |
|
Efficiency (pro Module): |
65% 2V/ -81% >5V/ -85% >7V -87% >12V/ -90% >48V with 385VDC input voltage |
|
|
|
M T B F, cooled by:
Water, 30°C inflow:
Forced Air, 30°C entrance: |
Conditions: 3kW DC output with 80% efficiency (600W internal power dissipation: WORST CASE)
ca. 120,000 h , put through > 50l/h for <10°C DT of cooling water. Minimum differential pressure >0.5 bar, abs. max. pressure <15bar
ca. 90,000 h , put through > 153m3/h for <15°C DT of cooling air, ambient air pressure 1 bar. Adequate airflow isroughlyy 1,4m/s.
Values for air cooled units are valid for new ones. Abrasive dust, corrosion, etc. can limiting the heat transfer to the cooling air during lifetime. Higher operating temperature is the consequence.
Increasing of internaltemperater at the most critical points of 10°C will reduce the MTBF by 50% Lower operationtemperaturess will increase the MTBFaccordinglyy, independent of cooling medium. |
|
|
|
Construction features, Accessories: |
|
3 U box with extraction lever: |
max. 6 modules, up to 3 kW/3,6kW output power |
|
Connections / plugs: |
24 female pins 80A, parallel used for higher currents, 3 x 9pin Sub D for sensing (each for 4 channels) |
|
Size (wxhxd): |
434mm x 132mm x 325 mm | |
|
Accessories:
|
|
19" Power Bin for plug in MARATON power supplies. 24 power contacts with M5 threated bolts and sense terminals at rearside. |
|
Type 44 : |
4U x 450mm mounting depth, 1 U air baffle, strain relief, cooling air entry front- or bottom side, for 3U - Box |
Special power bins / 19'' assembly with 3U and 6U (for two MARATON boxes) available. 450mm mounting depth |
|
|
|
|
|
|
|
 |
MARATON front side |
|
|
|
 |
Maraton with view on DC power and sense terminal | |
|
|
|
 |
Maraton rear side | |
|
|
 |
Maraton power supply | | |